Emerson Rosemount 3051 Reference Manual page 105

Pressure transmitter with hart protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Reference Manual
00809-0100-4001, Rev JA
Message
4k snsr EEPROM
error-factory ON
4k snsr EEPROM
error-user ON
Add item for ALL device types or only for
this ONE device type.
Command Not Implemented
Communication Error
Configuration memory not compatible
with connected device
CPU board not initialized ON
CPU EEPROM write failure ON
Device Busy
Device Disconnected
Device write protected
Device write protected. Do you still want
to shut off?
Display value of variable on hotkey
menu?
Download data from configuration
memory to device
Exceed field width
Exceed precision
Ignore next 50 occurrences of status?
Illegal character
Illegal date
Illegal month
Illegal year
Incompatible CPU board and module ON
Incomplete exponent
Incomplete field
Troubleshooting
Description
Replace the transmitter.
Use the Field Communicator to reset the temperature
units and the calibration type.
Asks the user whether the hot key item being added
should be added for all device types or only for the type of
device that is connected.
The connected device does not support this function.
The communicator and the device are not
communicating correctly. Check all connections between
the Field Communicator and the device and resend the
information.
The configuration stored in memory is incompatible with
the device to which a transfer has been requested.
The electronics board is not initialized.
Replace the electronics board.
Message sent to electronics board from HART signal
failed. Replace the electronics board.
The connected device is busy performing another task.
The device failed to respond to a command. Check all
connections between the Field Communicator and the
device and resend the command.
Device is in write-protect mode. Data can not be written.
Device is in write-protect mode. Press YES to turn the Field
Communicator off and lose the unsent data.
Asks whether the value of the variable should be displayed
adjacent to its label on the hotkey menu if the item being
added to the hotkey menu is a variable.
Press the SEND softkey to transfer information from the
communicator memory to the device.
Indicates that the field width for the current arithmetic
variable exceeds the device-specified description edit
format.
Indicates that the precision for the current arithmetic
variable exceeds the device-specified description edit
format.
Select YES to ignore the next 50 occurrences of device
status, or select no to display every occurrence.
An invalid character for the variable type was entered.
The day portion of the date is invalid.
The month portion of the date is invalid.
The year portion of the date is invalid.
Upgrade the electronics board or the sensor module to
the current revision.
The exponent of a scientific notation floating point
variable is incomplete.
The value entered is not complete for the variable type.
Section 5: Troubleshooting
November 2012
95