Emerson Rosemount 3051 Reference Manual page 189

Pressure transmitter with hart protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Reference Manual
00809-0100-4001, Rev JA
N1
Specific Conditions for Safe Use (X):
Japanese certifications
E4
Certificate
TC15850
TC15851
TC15854
TC15855
TC15856
TC15857
I4
IECEx certifications
E7
Process
Temp
-50 to 65
-50 to 80
Product certifications
ATEX Non-incendive/Type n and Dust
Certification No.: BAS 00ATEX3105X
Applicable Standards: IEC60079-0:2011, EN60079-15:2010, EN60079-31:2009
II 3 GD, Ex nA IIC Gc T5 (–40  Ta  70 °C),
Markings:
Ex ta IIIC T50 °C T
60°C Da, IP66
500
1180
1.) The apparatus is not capable of withstanding the 500 V insulation test required by
EN60079-15. This must be taken into account when installing the apparatus.
2.) This device contains a thin wall diaphragm. Installation, maintenance, and use shall
take into account the environmental conditions to which the diaphragm will be
subjected. The manufacturer's instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime. In case of repair, contact
the manufacturer for more information on the dimensions of the flameproof joints.
TIIS Flame-Proof
Description
3051C/D/1 4–20 mA HART — no meter
3051C/D/1 4–20 mA HART — with meter
3051T/G/1 4–20 mA HART, SST, Silicon — no meter
3051T/G/1 4–20 mA HART, Alloy C-276, Silicon — no meter
3051T/G/1 4–20 mA HART, SST, Silicon — with meter
3051T/G/1 4–20 mA HART, Alloy C-276, Silicon — with meter
Markings: Ex d IIC T6
TIIS Intrinsic Safety
Certification No.: TC16406
Markings: Ex ia IIC T4
IECEx Flame-proof
Certification No.: IECEx KEM 09.0034X
Applicable Standards: IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-26:2006,
Markings: Ex d IIC T5...T6 Ga/Gb, T5 (-50 °C  Ta  80 °C)/T6 (-50 °C  Ta  65 °C)
Ambient
Temp
-50 to 65
-50 to 80
Conditions of Certification (X):
1.) This device contains a thin wall diaphragm. Installation, maintenance, and use shall
take into account the environmental conditions to which the diaphragm will be
subjected. The manufacturer's instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
Temp Class
T6
T5
Appendix B: Product Certifications
November 2012
179