B.5

Hazardous locations certifications

B.5.1

North american certifications

FM Approvals
E5
I5
CSA international
All CSA hazardous location approved transmitters are certified to ANSI/ISA 12.27.01-2003.
E6
I6
Product certifications
Explosion-Proof and Dust Ignition Proof
Certificate No: 0T2H0.AE
Applicable Standards: FM Class 3600 – 1998, FM Class 3615 – 2006, FM Class 3810 –
2005, ANSI/NEMA 250 - 2003
Markings: Explosion-Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition-Proof for Class II, Division 1, Groups E, F, G; and Class III, Division 1.
T5 (Ta = -50 °C to +85 °C), Factory Sealed, Enclosure Type 4x
Intrinsically Safe and Non-Incendive
Certificate No: 1Q4A4.AX
Applicable Standards: FM Class 3600 – 1998, FM Class 3610 – 2010, FM Class 3611 –
2004, FM Class 3810 – 2005
Markings: Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D; Class II,
Division 1, Groups E, F, and G; Class III, Division 1 when connected per Rosemount
drawing 03031-1019 and 00375-1130 (When used with a Field Communicator);
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
Temperature Code: T4 (Ta = -50 °C to +40 °C), T3 (Ta = -50 °C to +85 °C), Enclosure Type
4x.
Special Conditions for Safe Use:
1.) The Rosemount 3051 transmitter housing contains aluminum and is considered a
potential risk of ignition by impact or friction. Care must be taken into account during
installation and use to prevent impact and friction.
2.) The Rosemount 3051 transmitter with the transient terminal block (Option code T1)
will not pass the 500Vrms dielectric strength test and this must be taken into account
during installation.
Explosion-Proof, Dust Ignition Proof and Class I Division 2
Certificate No.: 1053834
Applicable Standards: CSA Std. C22.2 No. 142 – M1987, CSA Std. C22.2 No. 30 – M1986,
CSA Std. C22.2 No. 213 – M1987, ANSI/ISA 12.27.01-2003.
Markings: Explosion-Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G.
Suitable for Class I, Division 2 Groups A, B, C, and D. Enclosure type 4X, factory sealed.
Single Seal (See Drawing 03031-1053).
Intrinsically Safe
Certificate No.: 1053834
Applicable Standards: CSA Std. C22.2 No. 142 – M1987, CSA Std. C22.2 No. 157 – 92,
ANSI/ISA 12.27.01-2003.
Markings: Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in
accordance with Rosemount drawings 03031-1024. Temperature Code T3C. Enclosure
Type 4X, Single Seal. Single Seal (See Drawing 03031-1053).
Appendix B: Product Certifications
November 2012
177