Section 2: Installation
November 2012
2.9
Electrical considerations
Note
Make sure all electrical installation is in accordance with national and local code requirements.
2.9.1
Conduit installation
If all connections are not sealed, excess moisture accumulation can damage the
transmitter. Make sure to mount the transmitter with the electrical housing positioned
downward for drainage. To avoid moisture accumulation in the housing, install wiring with
a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit
connections or the transmitter housing.
Recommended conduit connections are shown in
Figure 2-15. Conduit installation diagrams.
Possible
Conduit Line
Positions
Sealing
Compound
CORRECT
22
Figure
2-15.
Sealing
Compound
Possible
Conduit Line
Positions
CORRECT
Reference Manual
00809-0100-4001, Rev JA
Conduit
Lines
INCORRECT
Installation