Selection

3.1.6 Relay Option MCB 105

The MCB 105 option includes 3 pieces of SPDT contacts and must be fitted into option slot B.
3
3
Electrical Data:
Max terminal load (AC-1)
Max terminal load (AC-15)
Max terminal load (DC-1)
Max terminal load (DC-13)
Min terminal load (DC)
Max switching rate at rated load/min load
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately, it includes:
Relay module MCB 105
Extended LCP frame and enlarged terminal cover
Label for covering access to switches S201, S202 and S801
Cable strips for fastening cables to relay module
Adding the MCB 105 option:
1.
Disconnect the power to the live part connections on relay terminals.
2.
Do not mix live parts with control signals (PELV).
3.
Select the relay functions in 5-40 Function Relay [6-8], 5-41 On Delay, Relay [6-8] and 5-42 Off Delay, Relay [6-8].
NOTICE!
(Index [6] is relay 7, index [7] is relay 8, and index [8] is relay 9)
Relay 7
1
2
Figure 3.3 Relay Locations
58
Design Guide
1)
(Resistive load)
1)
(Inductive load @ cosφ 0.4)
1)
(Resistive load)
1)
(Inductive load)
Relay 8
Relay 9
NC
NC
NC
3
4
5
6
7
8
9
10
Danfoss A/S © Rev. 2014-01-13 All rights reserved.
11
12
240 V AC 2A
240 V AC 0.2 A
24 V DC 1 A
24 V DC 0.1 A
5 V 10 mA
-1
-1
6 min
/20 s
MG16C122