How to Install
Terminal Locations - Frame Size F2 and F4
Take the following position of the terminals into consideration when designing the cable access.
FASTENER TORQUE: MIO 19 Nm (14 FT -LB)
U/T1 96
V/T2 97
W/T3 98
Figure 5.76 Terminal Locations - Inverter Cabinet - F2 and F4. Connector Plate is 1.65 in [42 mm] below .0 Level.
1
Front Side
2
Left Side
Table 5.58 Legend to Figure 5.76
Figure 5.77 Regeneration Terminal Locations - F2 and F4
MG16C122
Design Guide
1
FASTENER TORQUE: MIO 19 Nm (14 FT -LB)
FASTENER TORQUE: MIO 19 Nm (14 FT -LB)
U/T1 96
V/T2 97
W/T3 98
U/T1 96
V/T2 97
W/T3 98
6
3
4
DC '-'
1739.1
1203.2
1163.2
1694.1
DC '+'
1654.1
1098.1
Danfoss A/S © Rev. 2014-01-13 All rights reserved.
2
4
308.3 [12.14]
253.1 [9.96]
180.3 [7.10]
5
0.0 [0.00]
4
Right Side
Ground bar
3
143
5
5