How to Order
4.1.2 Type Code String
1
2
3
4
F C
-
Figure 4.1 Example Type Code
4
4
Description
Product Group
Drive Series
Generation Code
Power Rating
AC Line Voltage
Enclosure
RFI filter
Brake
Display
Coating PCB
Line Power Option
Adaptation
Adaptation
Software release
72
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20
0
T
Position
1–3
4–6
7
8–10
11–12
13–15
16–17
18
19
20
21
22
23
24–27
Danfoss A/S © Rev. 2014-01-13 All rights reserved.
Design Guide
21
22
23
24
H
X
X
S
Possible Choice
FC
102
N
75–400 kW
T4: 380–480 V AC
T7: 525–690 V AC
E20: IP20 (chassis - for installation in external enclosure)
E2S: IP20/Chassis, D3h Frame
C2S: IP20/Chassis, D3h Frame, stainless steel backchannel
E21: IP21 (NEMA 1)
E2D: IP 21 (NEMA 1), D1h Frame
E5D: IP54 (NEMA 12), D1h Frame
E54: IP54 (NEMA 12)
E2M: IP21 (NEMA 1) with line power shield
E5M: IP54 (NEMA 12) with line power shield
C20: IP20 (chassis) + stainless steel backchannel
H21: IP21 (NEMA 1) + heater
H54: IP54 (NEMA 12) + heater
H2: RFI filter, class A2 (standard)
1)
H4: RFI filter class A1
X: No brake IGBT
B: Brake IGBT mounted
T: Safe torque off
U: Brake chopper + safe torque off
R: Regeneration terminals
S: Brake + regeneration (IP 20 only)
G: Graphical local control panel
N: Numerical local control panel
X: No local control panel
C: Coated PCB
R: Ruggedized PCB
X: No line power option
3: Line power disconnect and fuse
4: Line power contactor + fuses
7: Fuse
A: Fuse and load sharing (IP20 only)
D: Load share terminals (IP20 only)
E: Line power disconnect + contactor + fuses
J: Circuit breaker + fuses
X: Standard cable entries
Q: Heatsink access panel
X: No adaptation
Current software
25
26
27
28 29
30
31
32
33
34
X
X
X
X
A
B
C
35
36
37
38 39
D