Lifting - Danfoss VLT HVAC Drive FC 102 Design Manual

110–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Install
5
5
Figure 5.30 Fastener Location Detail
1 M8x60 mm bolt
2 M10x30 mm bolt
Table 5.24 Legend to Figure 5.30

5.1.6 Lifting

Lift the adjustable frequency drive using the dedicated
lifting eyes. For all E2 (IP00) enclosures, use a bar to avoid
bending the lifting holes of the adjustable frequency drive.
The following figures demonstrate the recommended
lifting methods for the different frame sizes. In addition to
Figure 5.33, Figure 5.34, and Figure 5.35, a spreader bar is an
acceptable way to lift the F-frame.
WARNING
The lifting bar must be able to handle the weight of the
adjustable frequency drive. See chapter 5.1.1 Mechanical
Dimensions for the weight of each frame size. Maximum
diameter for the bar is 1 in [2.5 cm]. The angle from the
top of the drive to the lifting cable should be 60° or
greater.
108
1
2
Danfoss A/S © Rev. 2014-01-13 All rights reserved.
Design Guide