How to Read this Design Gui...
VT Characteristics
Variable torque characteristics used for pumps and fans.
plus
VVC
Compared with standard voltage/frequency ratio control,
Voltage Vector Control (VVC
plus
and stability, both when the speed reference is changed
and in relation to the load torque.
60° AVM
Switching pattern called 60°Asynchronous Vector
Modulation (See 14-00 Switching Pattern).
The power factor is the relation between I
3 ×
U × I 1 × COS ϕ
Power factor =
3 ×
U × IRMS
The power factor for 3-phase control:
I
cos ϕ1
I
×
1
1
=
=
since cos ϕ1 = 1
I
I
RMS
RMS
The power factor indicates to what extent the adjustable
frequency drive imposes a load on the line power supply.
The lower the power factor, the higher the I
same kW performance.
I 1 2
I 5 2
I 7 2
I n 2
IRMS
=
+
+
+ . . +
In addition, a high power factor indicates that the different
harmonic currents are low.
The built-in DC coils produce a high power factor, which
minimizes the imposed load on the line power supply.
MG16C122
Design Guide
) improves the dynamics
and I
.
1
RMS
for the
RMS
Danfoss A/S © Rev. 2014-01-13 All rights reserved.
1
1
13