Danfoss VLT HVAC Drive FC 102 Design Manual page 228

110–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

General Specifications and ...
Alarm Word and Extended Status Word
Bit
Hex
0
00000001
1
00000002
2
00000004
3
00000008
4
00000010
5
00000020
6
00000040
7
00000080
8
00000100
9
00000200
10
00000400
11
00000800
12
00001000
13
00002000
14
00004000
15
00008000
8
8
16
00010000
17
00020000
18
00040000
19
00080000
20
00100000
21
00200000
22
00400000
23
00800000
24
01000000
25
02000000
26
04000000
27
08000000
28
10000000
29
20000000
30
40000000
31
80000000
Table 8.19 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional serial communication
bus for diagnosis. See also 16-90 Alarm Word, 16-92 Warning Word and 16-94 Ext. Status Word.
226
Design Guide
Dec
Alarm Word
1
Brake Check
2
Pwr. Card Temp
4
Ground Fault
8
Ctrl.Card Temp
16
Ctrl. Word TO
32
Overcurrent
64
Torque Limit
128
Motor Th Over
256
Motor ETR Over
512
Inverter Overld.
1024
DC undervolt
2048
DC overvolt
4096
Short Circuit
8192
Inrush Fault
16384
Mains ph. Loss
32768
AMA Not OK
65536
Live Zero Error
131072
Internal Fault
262144
Brake Overload
524288
U phase Loss
1048576
V phase Loss
2097152
W phase Loss
4194304
Fieldbus Fault
8388608
24 V Supply Low
16777216
Mains Failure
33554432
1.8 V Supply Low
67108864
Brake Resistor
134217728
Brake IGBT
268435456
Option Change
536870912
Drive Initialized
1073741824
Safe torque off
2147483648
Mech. brake low (A63)
Danfoss A/S © Rev. 2014-01-13 All rights reserved.
Warning Word
Brake Check
Pwr. Card Temp
Ground Fault
Ctrl.Card Temp
Ctrl. Word TO
Overcurrent
Torque Limit
Motor Th Over
Motor ETR Over
Inverter Overld.
DC undervolt
DC overvolt
DC Voltage Low
DC Voltage High
Mains ph. Loss
No Motor
Live Zero Error
10 V low
Brake Overload
Brake Resistor
Brake IGBT
Speed Limit
Fieldbus Fault
24 V Supply Low
Mains Failure
Current Limit
Low Temp
Voltage Limit
Unused
Unused
Unused
Extended Status Word
Extended Status Word
Ramping
AMA Running
Start CW/CCW
Slow-down
Catch Up
Feedback High
Feedback Low
Output Current High
Output Current Low
Output Freq High
Output Freq Low
Brake Check OK
Braking Max
Braking
Out of Speed Range
OVC Active
MG16C122