Output Control
3-5-2

Comparison Mode

Example Comparison Mode with Linear Counter
Note
The Counter Output Patterns of Counters which are configured to use no (i.e.
zero) Ranges, are ignored in the AND-calculation of the Unit Output Pattern. Like
this, Counters that you do not want to use, do not influence the AND-calculation of
the Unit Output Pattern. If both the Counters are configured to use no Ranges, the
output patterns for both outputs will be all OFF.
If the Unit is configured to control the Outputs in Comparison Mode, this Mode can
be applied to Circular Counters or Linear Counters (refer to 3-2-2 "Circular Coun-
ter" and 3-2-3 "Linear Counter" for more information).
Minimum Count Limit
−2,147,483,648
(=80000000
Output 0
Output 1
Soft Output 2
Soft Output 3
= Set in positive (+) direction
= Set in negative (−) direction
CV
1
2
3
4
5
6
7
In this example 7 Comparison Values are specified. On reaching a Comparison
Value an Output can be Set or Reset depending on the crossing direction. If the
CV is crossed in the positive counting direction (+CV crossing) or negative count-
)
H
Counter Value
CV1
CV2
CV3
Value
CV Crossing
+CV crossing
−87,000
−CV crossing
+CV crossing
−56,000
−CV crossing
+CV crossing
−15,000
−CV crossing
+CV crossing
+18,000
−CV crossing
+CV crossing
+46,000
−CV crossing
+CV crossing
+70,000
−CV crossing
+CV crossing
+108,000
−CV crossing
Maximum Count Limit
0
CV4
CV5
CV6
= Reset in positive (+) direction
= Reset in negative (−) direction
Out0
Out1 Soft2 Soft3
R
R
S
S
S
R
R
S
Section 3-5
+2,147,483,647
(=7FFFFFFF
)
H
CV7
R
S
R
73