Memory Allocation
Word
m+7
00-07
08-15
m+8
00-07
08-15
m+9
00-15
m+10
00-15
m+11
00-15
m+12
00-15
m+13 to m+16
00-15
106
Bit
Item
Input Noise Filter
Counters
---
Input Noise Filter
Digital Inputs
---
Output Pulse Turn
ON-Delay Time
Digital Output 0
Output Pulse Duration
Digital Output 0
Output Pulse Turn
ON-Delay Time
Digital Output 1
Output Pulse Duration
Digital Output 1
Reserved.
Select Noise Filter for Counters 1 and 2:
00 = 50 kHz (default)
01 = 500 kHz
02 = 10 kHz
Not used
Select Noise Filter for Digital Inputs 0 and 1:
00 = 50 kHz (default)
01 = 10 kHz
Not used
Define Output Pulse Turn ON-Delay time:
[0, 9999
ms]
(BCD)
Define Output Pulse Duration:
[0, 9999
ms]
(BCD)
0 = infinite duration (i.e. Output Pulse Duration function is
disabled)
Define Output Pulse Turn ON-Delay time:
[0, 9999
ms]
(BCD)
Define Output Pulse Duration: [0, 9999
0 = infinite duration (i.e. Output Pulse Duration function is
disabled)