Grounding; Bat-F; Bat-Rail - Hirschmann BAT54-F User Manual

Dual-band industrial access point / access client / access bridge bat family
Hide thumbs Also See for BAT54-F:
Table of Contents

Advertisement

2.10

Grounding

2.10.1

BAT-F

A separate anti-torsion screw connector on the housing is provided for the
functional ground (FE). It is indicated by the functional ground symbol. The
functional ground is electrically connected to the switching ground and to the
metal housing of the device.
For the ground wire, use a copper wire with a minimum cross section of
2
4 mm
to 6 mm
terminal sleeve used), and implement the grounding of the device via the
screw connector.
Clamp the ground wire between the two rectangular fastening plates - as
shown in the figure below - and fasten the screw.
Make sure that the ground wire is not in direct contact with the aluminum
housing of the device.
1
1
2
Figure 16: BAT54-F ground connection
1 - Fastening plates for ground wire
2 - Ground wire
2.10.2

BAT-Rail

The lower panel of the device housing is grounded by means of the DIN rail.
BAT-F, BAT-Rail, BAT54, BAT300
Release 02 07/10
2
(for North America: AWG 11 to AWG 9) (including any
41