Danfoss VT2800 Series Design Manual page 84

Table of Contents

Advertisement

221 Current limit, I
LIM
(CURRENT LIMIT)
Value:
0 - XXX.X % of par. 105
Function:
In this parameter, the maximum output current I
is set. The factory-set value corresponds to the
maximum output current I
is to be used as motor protection, set the rated
motor current. If the current limit is set above 100%
(the rated output current of the frequency converter,
I
), the frequency converter can only handle a load
INV.
intermittently, i.e. for short periods at a time. After the
load has been higher than I
for a period the load is lower than I
if the current limit is set at a lower value than I
acceleration torque will be reduced to the same extent.
Description of choice:
Set the required maximum output current I
223 Warning: Low current, I
(WARN. CURRENT LO)
Value:
0.0 - par. 224 Warning: High current, I
Function:
If the output current falls below the preset
limit I
a warning is gi v en.
LOW
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and
after a stop command or during stop.The warning
functions are acti v ated when the output frequency
has reached the resulting reference. The signal
outputs can be programmed to gi v e a warning signal
via terminal 46 and via the relay output.
Description of choice:
The lower signal limit of the output current I
must be programmed within the normal working
range of the frequency converter.
= factory setting. () = display text [] = value for use in communication via serial communication port
84
160 %
LIM
. If the current limit
MAX
, it must be ensured that
INV.
Please note that
INV.
, the
INV.
.
LIM
LOW
0.0 A
HIGH
LOW
®
VLT
2800 Series
224 Warning: High current, I
(WARN. CURRENT HI)
Value:
0 - I
MAX
Function:
If the output current exceeds the preset limit
I
a warning is gi v en.
HIGH
Parameters 223-228 Warning functions do not
work during ramp-up after a start command and
after stop command or during stop. The warning
functions are acti v ated when the output frequency
has reached the resulting reference. The signal
outputs can be programmed to gi v e a warning signal
via terminal 46 and via the relay output.
Description of choice:
The output current's upper signal limit I
be programmed within the frequency converter's
normal operating range. See drawing at parameter
223 Warning: Low current, I
225 Warning: Low frequency, f
(WARN.FREQ. LOW)
Value:
0.0 - par. 226
Warn.: High frequency, f
Function:
If the output frequency falls below the preset
limit f
, a warning is gi v en.
LOW
Parameters 223-228 Warning functions are out of
function during ramp-up after a start command and
after stop command or during stop. The warning
functions are acti v ated when the output frequency
has reached the resulting reference. The signal
MG.28.E9.02 - VLT is a registered Danfoss trademark
HIGH
I
MAX
must
HIGH
.
LOW
LOW
0.0 Hz
HIGH