LCP 2 control panel. First all parameter values are
copied to the LCP 2 control panel, which can then
be moved to another frequency converter. Here all
parameter values can be copied from the LCP 2
control unit to the frequency converter.
Setup shift
- Selection of Setup via terminals 29 and 33.
Par. 305 Digital input = Selection of Setup, lsb [31]
Par. 307 Digital input = Selection of Setup, msb [32]
Par. 004 Acti v e setup = Multi Setup [5]
004 Active Setup
(ACTIVE SETUP)
Value:
Factory Setup (FACTORY SETUP)
Setup 1 (SETUP 1)
Setup 2 (SETUP 2)
Setup 3 (SETUP 3)
Setup 4 (SETUP 4)
Multi Setup (MULTI SETUP)
Function:
The acti v e parameter Setup is selected here. All
parameters can be programmed in four indi v idual
parameter Setups. Shifts between Setups can
be made in this parameter via a digital input
or via serial communication.
Description of choice:
Factory Setup [0] contains the factory-set parameter
values. Setup 1-4 [1]-[4] are four indi v idual
Setups which can be selected as required. Multi
Setup [5] is used where remote-controlled shifts
between the four Setups via a digital input or via
serial communication is required.
005 Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP)
Setup 1 (SETUP 1)
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
VLT
Setup 2 (SETUP 2)
Setup 3 (SETUP 3)
Setup 4 (SETUP 4)
Acti v e Setup (ACTIVE SETUP)
Function:
You can select which Setup you want to programme
during operation (applies both via the control
panel and the serial communication port). It is,
for example, possible to programme Setup 2
[2], while the acti v e Setup is set to Setup 1 [1]
in parameter 004 Acti v e Setup .
Description of choice:
Factory Setup [0] contains the factory-set data
and can be used as a source of data if the
other Setups are to be reset to a known status.
Setup 1-4 [1]-[4] are indi v idual Setups that can
be programmed freely during operation. If Acti v e
Setup [5] is selected, the programming Setup will
be equal to parameter 004 Acti v e Setup.
NB!:
If data is modified or copied to the acti v e
Setup, the modifications have an immediate
effect on the unit's operation.
[0]
[1]
006 Setup copying
[2]
(SETUP COPY)
[3]
Value:
[4]
No copying (NO COPY)
[5]
Copy to Setup 1 from #
(COPY TO SETUP 1)
Copy to Setup 2 from #
(COPY TO SETUP 2)
Copy to Setup 3 from #
(COPY TO SETUP 3)
Copy to Setup 4 from #
(COPY TO SETUP 4)
Copy to all Setups from # (COPY TO ALL)
Function:
You can copy from the selected acti v e Setup in
parameter 005 Programming setup to the selected
Setup or Setups in this parameter.
NB!:
Copying is only possible in Stop (motor stopped
in connection with a stop command).
Description of choice:
Copying begins when the required copying function
has been selected and the [OK]/[CHANGE DATA]
[0]
[1]
®
2800 Series
[2]
[3]
[4]
[5]
[0]
[1]
[2]
[3]
[4]
[5]
61