Select Special motor mode [8], if a special U/f
setting is needed that is to be adapted to the
present motor. The break points are set in
parameters 423-428 Voltage/frequency .
NB!:
Please note that if a value set in the nameplate
parameters 102-106 is changed, there will
be an automatic change of parameter 108
Stator resistance and 109 Stator reactance.
102 Motor power P
M,N
(MOTOR POWER)
Value:
0.25 - 22 kW
Function:
Here you must set a power value [kW] P
corresponding to the motor's rated power. The
factory sets a rated power value [kW] P
that depends on the type of unit.
Description of choice:
Set a value that matches the nameplate data on the
motor. Settings between one size below and one
size over the factory setting are possible.
103 Motor voltage U
M,N
(MOTOR VOLTAGE)
Value:
For 200 V units: 50 - 999 V
For 400 V units: 50 - 999 V
Function:
This is where to set the rated motor voltage
U
for either star Y or delta
M,N
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
Select a value that corresponds to the nameplate
data on the motor, regardless of the frequency
converter's mains voltage.
This is where to select the rated motor frequency f
Select a value that corresponds to the nameplate
data on the motor.
The nominal, rated current of the motor I
part of the frequency converter calculation of features
Depends on unit
such as torque and motor thermal protection.
,
M,N
Set a value that corresponds to the nameplate
data on the motor. Set the motor current
,
M,N
I
star-connected Y or delta-connected
This is where to set the value that corresponds
230 V
to the rated motor speed n
seen from the nameplate data.
400 V
Select a value that corresponds to the nameplate
data on the motor.
.
®
VLT
2800 Series
Description of choice:
104 Motor frequency f
(MOTOR FREQUENCY)
Value:
24-1000 Hz
Function:
Description of choice:
105 Motor current I
M,N
(MOTOR CURRENT)
Value:
0,01 - I
Depends on choice of motor
MAX
Function:
Description of choice:
taking into account whether the motor is
M,N
106 Rated motor speed
(MOTOR NOM. SPEED)
Value:
100 - f
x 60 (max. 60000 rpm)
M,N
Depends on parameter 104 Motor frequency, f
Function:
Description of choice:
M,N
50 Hz
M,N
forms
M,N
.
M,N
that can be
M,N
69
.