Danfoss VT2800 Series Design Manual page 65

Table of Contents

Advertisement

Shifting from Remote control to Local control in
parameter 002 Local/remote operation, while this
parameter has been set to Remote-operated control
as parameter 100 [4]: the present reference will
be maintained. If the reference signal is negati v e,
the local reference will be set to 0.
Shifting from Local operation to Remote operation
in parameter 002 Local/remote operation, while
this parameter has been set to Remote operation:
The local reference will be replaced by the
remote-operated reference signal.
014 Local stop
(LOCAL STOP)
Value:
Not acti v e (DISABLE)
Acti v e (ENABLE)
Function:
In this parameter, the local [STOP]-key can be
engaged or disengaged on the control panel
and on the LCP control panel.
Description of choice:
If Not acti v e [0] is selected in this parameter,
the [STOP]-key will be inacti v e.
NB!:
If Not acti v e [0] is selected, the motor cannot
be stopped by means of the [STOP]-key.
015 Local jog
(LOCAL JOGGING)
Value:
Not acti v e (DISABLE)
Acti v e (ENABLE)
Function:
In this parameter, the jog function on the LCP
control panel can be engaged/disengaged.
Description of choice:
If Not acti v e [0] is selected in this parameter,
the [JOG]-key will be inacti v e.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
VLT
016 Local reversing
(LOCAL REVERSING)
Value:
Not acti v e (DISABLE)
Acti v e (ENABLE)
Function:
In this parameter you can select/deselect the reversing
function on the LCP control panel. The key can only
be used if parameter 002 Local/remote operation
is set to Local operation [1] and parameter 013
Localcontrol to Local control, open loop [1] or
Local control as parameter 100 [3].
Description of choice:
If Disable [0] is selected in this parameter, the
[FWD/REV] key will be disabled. See also parameter
200 Output frequency range.
[0]
[1]
017 Local reset of trip
(LOCAL RESET)
Value:
Not acti v e (DISABLE)
Acti v e (ENABLE)
Function:
In this parameter, the reset function on the control
panel can be engaged/disengaged.
Description of choice:
If Not acti v e [0] is selected in this parameter,
the reset function will be inacti v e.
NB!:
Select Not acti v e [0], only if an external reset
signal has been connected via the digital inputs.
[0]
[1]
018 Lock for data changes
(DATA CHANGE LOCK)
Value:
Not locked (NOT LOCKED)
Locked (LOCKED)
Function:
In this parameter, it is possible to 'lock' the controls
to disable data changes via the control keys.
Description of choice:
If Locked [1] is selected, data changes in the
parameters cannot be made; however, it will
still be possible to make data changes via serial
®
2800 Series
[0]
[1]
[0]
[1]
[0]
[1]
65