RFI 1B filter
All frequency converters will cause electromagnetic
noise in the mains supply when they are operating.
An RFI (Radio Frequency Interference) filter will reduce
the electromagnetic noise in the mains supply.
Without an RFI filter there is a risk that a frequency
converter will disrupt other electrical components
Technical data for VLT 2803-2875 RFI 1B filter
Max. cable length (screened/armoured) 200-240 V
Max. cable length (screened/armoured) 380-480 V
Enclosure
Max. rated current
Max. Voltage
Max. voltage to earth
Min. distance between VLT and RFI 1B filter
Min. distance above and below RFI 1B filter
Dimensions H x W x D (mm)
Weight
1)
For mechanical dimensions see under
Mechanical dimensions.
MG.28.E9.02 - VLT is a registered Danfoss trademark
1)
®
VLT
2800 Series
that are connected to the mains and might
thus cause operating disruption.
By fitting an RFI 1B filter module between the mains
supply and the VLT 2800, the VLT 2800 complies
with the EMC norm EN 55011-1B.
NB!:
To comply with EN 55011-1B the RFI 1B
filter module must be fitted together with a
VLT 2800 with integral 1A RFI filter.
100 m (At 1A: 100 m)
25 m (At 1A: 50 m)
IP 20
16 A
480 V AC
300 V AC
Side-by-Side
100 mm
200 x 60 x 87
0.9 kg
See ordering number for RFI 1B filter module
under Accessories for VLT 2800.