152 Maintenance

Maintenance intervals

The table below shows the maintenance tasks which can be done by the end user. The
complete maintenance schedule is available on the Internet
(www.abb.com/drivesservices). For more information, consult your local ABB Service
representative (www.abb.com/searchchannels).
Legend
I
Inspection (visual inspection and maintenance action if needed)
R
Replacement
P
Performance of on/off-site work (commissioning, tests, measurements or other work)
Recommended annual actions by the user
Air inlet and outlet meshes (IP22/IP42)
Cabinet door filters (IP54)
Ambient conditions (dustiness, moisture, corrosion, temperature)
Cleaning of heatsinks
Tightness of terminals
Quality of supply voltage
Air circuit breaker maintenance (if present)
Reforming DC circuit capacitors (spare modules and spare capacitors)
Spare parts
Cooling
Supply and inverter module main cooling fans
LCL filter module cooling fans
Sine filter (option +E206) cooling fan
Supply and inverter modules: circuit board compartment fan
Internal cabinet cooling fans (internal, door and IP54)
Batteries
Control panel battery
Control unit battery
Maintenance and component replacement intervals are based on the assumption that the
equipment is operated within the specified ratings and ambient conditions. ABB
recommends annual drive inspections to ensure the highest reliability and optimum
performance.
Note: Long term operation near the specified maximum ratings or ambient conditions may
require shorter maintenance intervals for certain components. Consult your local ABB
Service representative for additional maintenance recommendations.
Years from start-up
3
6
9
12
15
R
R
R
R
R
R
R
R
R
R
R
R
I
R
I
I
I
P
I
O
I
18
21
R
R
R
R
R
R
R