Maintenance

What this chapter contains

This chapter contains preventive maintenance instructions.

Safety

WARNING! Read the
performing any maintenance on the equipment. Ignoring the safety instructions can
cause injury or death.

Maintenance intervals

If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Capacitor reforming
Heatsink temperature check
and cleaning
Change of additional cooling
fan.
Cooling fan change
Frame size R4 and up:
capacitor change

Heatsink

The heatsink fins pick up dust from the cooling air. The drive runs into
overtemperature warnings and faults if the heatsink is not clean. In a "normal"
environment (not dusty, not clean) the heatsink should be checked annually, in a
dusty environment more often.
Clean the heatsink as follows (when necessary):
1. Remove the cooling fan (see section Fan).
2. Blow clean compressed air (not humid) from bottom to top and simultaneously
use a vacuum cleaner at the air outlet to trap the dust. Note: If there is a risk of
the dust entering adjoining equipment, perform the cleaning in another room.
3. Replace the cooling fan.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Safety instructions
Maintenance
Every year when stored
Depends on the dustiness of
the environment (every 6 to 12
months)
Every three years
Every six years
Every ten years
on the first pages of this manual before
Interval
See Reforming.
See Heatsink.
See
See Fan.
See Capacitors.
85
Instruction
Additional fan.
Maintenance