The diagnostics of the Safe torque off function cross-compare the status of the two STO
channels. In case the channels are not in the same state, a fault reaction function is
performed and the inverter trips on an "STO hardware failure" fault. An attempt to use the
STO in a non-redundant manner, for example activating only one channel, will trigger the
same reaction.
See the firmware manual of the inverter control program for the indications generated by
the inverter, and for details on directing fault and warning indications to an output on the
control unit for external diagnostics.
Any failures of the Safe torque off function must be reported to ABB.

Safety data

The safety data for the Safe torque off function is given below.
Note: The safety data is calculated for redundant use, and does not apply if both STO
channels are not used.
Frame
SIL/
SC
size
SILCL
1×R8i
3
3
2×R8i
3
3
3×R8i
3
3
4×R8i
3
3
5×R8i
3
3
6×R8i
3
3
The following temperature profile is used in safety value calculations:
670 on/off cycles per year with T = 71.66 °C
1340 on/off cycles per year with T = 61.66 °C
30 on/off cycles per year with T = 10.0 °C
32 °C board temperature at 2.0% of time
60 °C board temperature at 1.5% of time
85 °C board temperature at 2.3% of time.
The STO is a type B safety component as defined in IEC 61508-2.
Relevant failure modes:
The STO trips spuriously (safe failure)
The STO does not activate when requested
A fault exclusion on the failure mode "short circuit on printed circuit board" has been
made (EN 13849-2, table D.5). The analysis is based on an assumption that one
failure occurs at one time. No accumulated failures have been analyzed.
STO reaction time (shortest detectable break): 1 ms
STO response time: 2 ms (typical), 25 ms (maximum)
Fault detection time: Channels in different states for longer than 200 ms
Fault reaction time: Fault detection time + 10 ms
STO fault indication (parameter 31.22) delay: < 500 ms
STO warning indication (parameter 31.22) delay: < 1000 ms
PFH
SFF
PFD
(T
= 20 a)
PL
1
(T
(%)
(1/h)
e
>99
5.0E-11
4.5E-07
e
>99
6.2E-11
5.5E-07
e
>99
7.3E-11
6.5E-07
e
>99
8.4E-11
7.6E-07
e
>99
9.5E-11
8.6E-07
e
>99
1.1E-10
9.6E-07
The Safe torque off function 247
MTTF
PFD
D
avg
avg
= 2 a)
(T
= 5 a)
1
1
(a)
1.1E-06
23970
1.3E-06
16330
1.6E-06
12390
1.9E-06
9980
2.1E-06
8360
2.4E-06
7190
DC
Cat.
HFT
CCF
(%)
> 90
3
1
80
> 90
3
1
80
> 90
3
1
80
> 90
3
1
80
> 90
3
1
80
> 90
3
1
80
Lifetime
(a)
20
20
20
20
20
20