Descriptions of options

Note: All options are not available for all drive types, do not coexist with certain other
options, or may require additional engineering. Check actual availability with ABB.

Degree of protection

Definitions

According to IEC/EN 60529, the degree of protection is indicated by an IP code where the
first numeral means protection against ingress of solid foreign objects, and the second
numeral protection against ingress of water. The IP codes of the standard cabinet and
options covered in this manual are defined below.
IP code
IP22
against ingress of solid foreign objects >
12.5 mm diameter *
IP42
against ingress of solid foreign objects > 1 mm
IP54
dust-protected
* meaning for protection of persons: against access to hazardous parts with finger

IP22 (standard)

The degree of protection of the standard drive cabinet is IP22 (UL type 1). The air outlets
at the top of the cabinet and the air inlet gratings are covered with metallic gratings. With
doors open, the degree of protection of the standard cabinet and all cabinet options is
IP20. The live parts inside the cabinet are protected against contact with clear plastic
shrouds or metallic gratings.

IP42 (option +B054)

This option provides the degree of protection of IP42 (UL type 1). The air inlet gratings are
covered with a metallic mesh between the inner and outer metallic gratings.

IP54 (option +B055)

This option provides the degree of protection of IP54 (UL type 12). It provides the cabinet
air inlets with filter housings containing folded board air filter mats between the inner and
outer metallic gratings. An additional fan and filtered outlets on the cabinet roof are also
included.

Cooling air intake through bottom of cabinet (option +C128)

See page 72.

Channeled air outlet (option +C130)

This option provides a collar for connection to an air outlet duct. The collar is located on
the cabinet roof. Depending on the equipment installed in each cubicle, the channeled air
outlet either replaces, or adds to, the standard roof arrangement.
The option also provides the cabinet air inlets with filter housings containing folded board
air filter mats between the inner and outer metallic gratings.
See also
Air outlet duct on the cabinet roof (option +C130)
The equipment is protected ...
First numeral
Operation principle and hardware description 45
Second numeral
against dripping (15° tilting) water
against dripping (15° tilting) water
against splashing water
on page 73.