100 Application macros

Default control connections for the Sequential control macro

External power input
24 V DC, 1.6 A
Relay output RO1 [Ready]
250 V AC / 30 V DC
2 A
Relay output RO2 [Modulating]
250 V AC / 30 V DC
2 A
Relay output RO3 [Fault (-1)]
250 V AC / 30 V DC
2 A
+24 V DC
Digital input ground
+24 V DC
Digital input/output ground
DI/DIO grounding selection jumpers
Digital input DI1 [Stop/Start]
Digital input DI2 [Direction]
Digital input DI3 [Acc/Dec ramp 1/2 selection]
Digital input DI4 [Constant speed sel1]
Digital input DI5 [Constant speed sel2]
Digital input DI6 or thermistor input [Constant speed sel3]
Start interlock (0 = Stop)
Digital input/output DIO1 [Output: Ready]
Digital input/output DIO2 [Output: Running]
Reference voltage (+)
Reference voltage (–)
Ground
Analog input AI1 [EXT1 Reference (Speed ref1)]
(Current or voltage, selectable by jumper AI1)
Analog input AI2 (Current or voltage, selectable by jumper AI2)
AI1 current/voltage selection jumper
AI2 current/voltage selection jumper
Analog output AO1 [Current %]
Analog output AO2 [Speed %]
Drive-to-drive link termination jumper
Drive-to-drive link.
Safe torque off. Both circuits must be closed for the drive to start.
Control panel connection
Memory unit connection
+24VI
1
GND
2
NO
1
COM
2
NC
3
NO
4
COM
5
NC
6
NO
7
COM
8
NC
9
+24VD
1
DIGND
2
+24VD
3
DIOGND
4
DI1
1
DI2
2
DI3
3
DI4
4
DI5
5
DI6
6
DIIL
A
DIO1
1
DIO2
2
+VREF
1
-VREF
2
AGND
3
AI1+
4
AI1-
5
AI2+
6
AI2-
7
AI1
AI2
AO1+
1
AO1-
2
AO2+
3
AO2-
4
T
B
1
A
2
BGND
3
OUT1
1
OUT2
2
IN1
3
IN2
4