Torque Control Macro - ABB ACS850 Manual

Machinery drive
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

96 Application macros

Torque control macro

This macro is used in applications in which torque control of the motor is required.
Torque reference is given through analog input AI2, typically as a current signal in the
range of 0...20 mA (corresponding to 0...100% of rated motor torque).
The start/stop signal is connected to digital input DI1, direction signal to DI2. Through
DI3, it is possible to select speed control instead of torque control.
A constant speed (300 rpm) can be activated through DI4.
Default parameter settings for Torque control macro
Below is a listing of default parameter values that differ from those listed in chapter
Additional parameter data
Parameter
No.
Name
10.01
Ext1 start func
10.03
Ext1 start in2
10.04
Ext2 start func
10.05
Ext2 start in1
10.06
Ext2 start in2
10.10
Fault reset sel
12.01
Ext1/Ext2 sel
12.05
Ext2 ctrl mode
13.05
AI1 min scale
13.10
AI2 min scale
22.01
Acc/Dec sel
26.02
Const speed sel1
26.06
Const speed1
(page 263).
Torque control
macro default
In1St In2Dir
DI2
In1St In2Dir
DI1
DI2
C.FALSE
DI3
Torque
0.000
0.000
DI5
DI4
300 rpm