Failsafe Mode; Accessing Diagnostic Information - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

FAILSAFE Mode

Several of the internal diagnostics tests put the SVI II ESD into FAILSAFE mode if the errors
continue for a preset time. When SVI II ESD goes into FAILSAFE, the valve is driven to its
Failsafe position. It remains in that position until the cause of the error is cleared and the
instrument is reset.
Reset is performed in two ways:
Connect a HART
or
Turn the power off and on.
To prevent the valve from moving after reset:
Put the controller in manual, and set valve position setpoint to Failsafe position 0% if
ATO, 100% if ATC.
You can set a special case of FAILSAFE for use on critical loops to force the process to trip if a
positioner is unable to control the valve by:
Setting a Position Error Band and a Position Error Time 2 that forces valve to its failsafe
position if position error exceeds the band for a time longer than time 2.

Accessing Diagnostic Information

Whenever SVI II ESD encounters an error during any operation it is reported. Dependent upon
the interface used, the SVI II ESD determines how the error is reported:
LCD, errors appear on the LCD.
ESDVue, errors are reported when running diagnostic tests and on the Status screen.
HART
display.
136 |
=GE Oil & Gas
The positioner LCD may indicate Failsafe when an alarm condition
NOTE
exists. Use the pushbuttons to view and clear alarms. See
"Accessing Diagnostic Information" on page 136.
®
modem and ValVue ESD, and then click the RESET button.
®
handheld device, errors appears to the HART
®
handheld communicator
© 2016 General Electric Company. All rights reserved.