PST CONF (VIEW DATA) Menu

There are two instances of PST CONF (PST CONFiguration) contained in the display menus; one
instance can only be accessed from VIEW DATA, the other instance is accessed through
SETUP. PST CONF only displays the PST configuration data when accessed from VIEW DATA.
The PST configuration parameters viewable by pressing + and - are:
TRAVEL
PMIN: Pressure Units (PSI, BAR, KPA)
MAX TIME
RAMPSPEED
Viewing PST Configuration Parameters
To view PST configuration parameters use the following procedure:
1. If in NORMAL operating mode, press any button.
2. Press + to move through the options until you reach VIEW DATA menu item.
*
3. Press
mode, press + repeatedly until VIEW DATA menu item is reached. Press
DATA mode.
4. In VIEW DATA menu, press + repeatedly until the PST CONF menu item is reached. Press
to select PST CONF mode.
© 2016 General Electric Company. All rights reserved.
If you would like to configure Partial Stroke Testing (PST) refer to
NOTE
"PST Configuration" on page 116.
to go to VIEW DATA menu (This leaves the valve in NORMAL mode.). If in MANUAL
Masoneilan SVI II ESD Installation and Maintenance Manual
*
to select VIEW
*
| 109
=