Analog Safety Demand (Asd) Configuration; Discrete Safety Demand (Dsd) Configuration - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

Analog Safety Demand (ASD)
The Analog Safety Demand configuration is: 4 - 20 mA signal, power and trip signal with
superimposed HART
Control System
2 Wire Solution - Safety Function Triggered by Current Sensing (5.6mA = Safety Trip)
Discrete Safety Demand (DSD)
The Discrete Safety Demand configuration is: 24 VDC, power and trip signal with
superimposed HART
Control System
Safety System
© 2016 General Electric Company. All rights reserved.
®
communications (Figure 51).
AO
or
4 - 20 mA + HART
Safety System
Figure 51 Analog Safety Demand (ASD) Configuration
®
communications (Figure 53).
High Impedance
Device Required
for HART Signaling
DO
or
24 VDC + HART
Safety Function Triggered by Discrete 0 - 24 VDC Signal (3 VDC = Safety Trip)
Figure 52 Discrete Safety Demand (DSD) Configuration
SVI II ESD
.
SVI II ESD
Masoneilan SVI II ESD Installation and Maintenance Manual
| 75
=