VIEW DATA Menu

The VIEW DATA menu reads current configuration information, including PST configuration.
This information cannot be changed from the VIEW DATA menu. Exit from the VIEW DATA
menu to return to the previous menu.
This menu can be entered either from the MANUAL Mode menu or from NORMAL Mode menu.
When entering VIEW DATA from NORMAL mode the valve shall still respond to changes in set
point input signal and the displayed values change in accordance with input signal changes.
When entered from MANUAL mode, the valve is in locked position. The parameters viewable
by pressing + and - are:
SINGLE
ATO or ATC
PSI, BAR, KPA
Viewing Configuration Parameters
To view configuration parameters use the following procedure:
1. If in NORMAL operating mode, press any button.
2. Press + to move through options until you reach the VIEW DATA menu item.
*
3. Press
mode, press + repeatedly until the VIEW DATA menu item is reached. Press
VIEW DATA mode.
4. To exit from the VIEW DATA menu, press * at any menu line. You return to the last
displayed menu.
© 2016 General Electric Company. All rights reserved.
to go to VIEW DATA menu (This leaves the valve in NORMAL mode.). If in MANUAL
Masoneilan SVI II ESD Installation and Maintenance Manual
*
to select
| 107
=