8. Operation and Maintenance

Operational Overview

SVI II ESD is Masoneilan's solution to improve safety in a processing plant; it is designed to
prevent and mitigate possibly uncontrollable situations. SVI II ESD is a SIL 3 compliant Smart
Valve Interface that continuously monitors the ESD valve operation of the and reports any
operational failures.
An emergency shutdown valve is a valve that operates to insure a safe state of a plant when
process conditions become or could become uncontrollable. Hundreds of ESD valves are part of
every petro-chemical and offshore production plant, as well as part of pipeline installations.
During normal operation, these valves are energized to stay open, with the means of a solenoid
valve. If an unsafe situation occurs, the ESD valve is de-energized. The solenoid valve vents the
pressure from the actuator chamber, to atmosphere. The accumulated static energy in the
actuator spring, provides the necessary force to bring the valve to its closed position.
Because of it data monitoring capability due to its embedded sensors, SVI II ESD is capable of
validating the health of its integral components. The ESD valve partially stroking capacity while
in normal operations (energized to stay open), enables validation of valve and actuator assembly
health. Periodic ESD valve testing reduces PFD (probability of failure on demand) since exercising
the valve reduces the risk of improper operations due to sticking, and confirms if an impending
problem would prevent the ESD valve to properly operate.
The ESD device performs as a smart solenoid to pneumatically activate an ON/OFF valve.
It is primarily used for safety instrumented systems (SIS) that require field devices to be
certified for safety related applications according to IEC61508.
It is certified by TUV for usage to a SIL3 safety integrity level.
Interacts with a SIS Logic solver.
Works with existing 24 VDC, 2 wire installations with superimposed HART
communications
Works with a 4-20 mA signal, 2 wire installations with superimposed HART
communications
© 2016 General Electric Company. All rights reserved.
Masoneilan SVI II ESD Installation and Maintenance Manual
®
®
| 121
=