Calibration With Pushbutton Display - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

Calibration with Pushbutton Display

In order to calibrate SVI II ESD using the pushbutton display, it must be in SETUP mode. To
calibrate the SVI II ESD:
1. On power up, if SVI II ESD is not in NORMAL mode, switch to NORMAL mode. Display
alternates between POS and SIGNAL indicating NORMAL mode.
2. Press + to access MANUAL mode and MANUAL appears.
3. Press * to select the MANUAL mode and the display alternates between POS –M and SIG
indicating MANUAL mode.
4. Press * and SETUP appears.
5. Press * and
6. Press + to display
7. Select CALIB by pressing *. STOPS appears.
8. Press * to activate the Find Stops calibration procedure. The valve moves full open and
back to full closed. Observe all warnings.
9. Press * to cause the valve to stroke and to automatically calibrate valve travel.
10. Wait until STOPS procedure finishes, press + twice until TUNE appears.
© 2016 General Electric Company. All rights reserved.
Pilot Trim Valve Applications require the use of the Manual Stop
CAUTION
calibration procedure. Do not run Find Stops or ValVue ESD Setup
Wizard on valves with Pilot Trim or damage to the valve occurs.
Always perform configuration before running calibration
NOTE
functions.
CONFIG appears.
CALIB.
Masoneilan SVI II ESD Installation and Maintenance Manual
| 91
=

Advertisement

Table of Contents
loading

Table of Contents