5. Configuration and
Calibration
Overview
This section provides information on SVI II ESD setup and calibration procedures to ensure
proper valve positioning.
NOTE
SVI II ESD Setup
Pushbuttons and local display are thoroughly described in "Pushbuttons and Local Display" on
page 98 of this manual.
Using the Pushbuttons and Display
When configuring or calibrating a valve equipped with SVI II ESD, using the pushbutton display,
the following steps are recommended:
1. Change mode to Manual mode.
2. Examine and adjust all Configuration items.
3. Enter Calibration mode.
4. Run Stops to automatically calibrate stroke.
5. Run Auto Tune to set dynamic response.
6. Examine device Status.
7. Introduce manual set point changes to verify dynamic performance.
© 2016 General Electric Company. All rights reserved.
You should perform setup and calibration procedures in this section before putting
the SVI II ESD into operation as the SIF.
Masoneilan SVI II ESD Installation and Maintenance Manual