Calibration Menu
The Calibration menu shown in Figure 64 provides access to all of the calibration functions for
SVI II ESD. If a change is made in the Air-To-Open/Air-To-Close configuration option, or if you
move SVI II ESD to a different valve, or make any change to the valve position linkage, you
must run the find STOPS calibration again.
CAUTION: These functions stroke the valve over its full range.
CALIB
*
STOPS
*
RUNNING
*
FAILURE
If a calibration stops error occurs
FAILURE message appears. Press * briefly and
automatically return to STOPS starting point.
© 2016 General Electric Company. All rights reserved.
CALIBration Menu
Do not perform while the valve is controlling the process.
See Figure 62 on
page 102 for full menu
+
+
<VALUE>
STOP OP
*
*
<VALUE>
+/-
* - +
If a calibration tuning error occurs
FAILURE message appears. Press * briefly and
automatically return to TUNE starting point.
Figure 64 CALIBration Menu
+
TUNE
*
+/-
STEP 1/3
*
STEP 2/3
*
STEP 3/3
*
TUNE OK
FAILURE
Masoneilan SVI II ESD Installation and Maintenance Manual
+