Pst Setup With Valvue Esd; Pst Data From Esdvue; Pst Diagnostic Graph Example - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

PST Setup with ValVue ESD

When configuring PST with ValVue ESD, more parameters are available. You can configure
dwell time, friction low and high limits, breakout limit, droop limit and can freeze DO and AO
switches. ValVue ESD also provides the ability to schedule PST, so that PST automatically runs
at the scheduled time. See the help file.

PST Data from ESDVue

When using ESDVue to run PST, ESDVue provides PST feedback in a graphical format.
Examples of PST graphical data are shown in Figure 71 and Figure 72.
Breakout
Valve / Actuator
Friction / 2
Minimum
Allowed
Actuator
Pressure
During PST
118 |
=GE Oil & Gas
After you launch a connected device from ValVue ESD, the
NOTE
software tool changes to ESDVue. ValVue ESD is the main
interface for detecting and launching SIS devices. After a
connected device has been selected, the software tool for
connected device is ESDVue.
Figure 71 PST Diagnostic Graph Example
PST Range
© 2016 General Electric Company. All rights reserved.