Table 10 lists menus items and functional descriptions, including parameters if applicable.
Pushbutton Menu
NORMAL
MANUAL
SETUP
CONFIG
CALIB
PST CONF
VIEW DATA
VIEW ERR
CLR ERR
RUN PST
© 2016 General Electric Company. All rights reserved.
Table 10 Pushbutton Display Menus
Runs SVI II ESD in normal operating mode, displays position, signal and pressure.
Executes manual mode in which the valve does not respond to input signal and you can
adjust position manually. In MANUAL mode the valve responds to the Trip signal in addition to
®
responding to HART
. MANUAL mode menu provides access to SETUP.
SETUP menu provides access to lower level setup menus; configuration (CONFIG), calibration
(CALIB) and PST configuration.
Using CONFIG (configuration) menu you can set the following parameters: ATO/ATC, Pressure
units, display language.
Using CALIB (calibration) menu you can calibrate SVI II ESD by running STOPS (find stops) and
TUNE (autotune) functions.
Using PST CONF (PST configuration) menu you can configure the following PST parameters:
TRAVEL (adjustable from 0 to 100% of travel rating), PMIN (minimum allowed pressure during
PST), MAX TIME (maximum allowed time in seconds for partial stroke), PST SPEED (the valve
travel speed in% travel per second).
The VIEW DATA menu displays the parameters set in CONFIG and PST CONF.
The VIEW ERR menu displays all current errors.
The CLR ERR menu allows you to clear current errors, one at a time.
The RUN PST menu executes PST (Partial Stroke Testing)
Function/Parameters
Masoneilan SVI II ESD Installation and Maintenance Manual
| 99
=