APPENDIX A
SUMMARY OF LED OPERATION
GSMVLP4G Status Display Operation
The GSMVLP4G Status Display has four LEDs used to indicate message and device status (refer to
Figure 5). When installed in the control, the LEDs appear in the following order from top to bottom.
STATUS, green
•
MESSAGE, yellow
•
FAULT, red
•
MINIMUM SIGNAL STRENGTH, green
•
Each LED can have four different states - ON, OFF, FAST BLINK and SLOW BLINK. Throughout this
document, the key shown in Figure 4 is used to describe LED state:
Minimum Signal Strength LED Operation
The Minimum Signal Strength LED normally displays the module's signal strength. The LED (green
LED) will be lit to indicate that the minimum required signal strength for installation exists between
the module and the receiving tower. Refer to Figure 9.
Table 3. Status and Signal Strength LED Operation
LED COLOR
LED
GREEN
STATUS
YELLOW
MESSAGE
RED
FAULT
GREEN
MINIMUM
SIGNAL
STRENGTH
ALL (of the above)
Figure 8 – LED Key
ON – GSMVLP4G is NOT registered with AlarmNet.
OFF – GSMVLP4G is registered with AlarmNet.
FAST BLINK – Download session with Compass in progress.
SLOW BLINK – In unison with yellow LED – Registration in progress.
ON – Message transmission pending.
QUICK PERIODIC BLINK - Normal
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – In unison with green LED – Registration in progress.
ON – No contact with network.
OFF– Normal.
SLOW BLINK – Loss of communication with the panel (ECP fault).
FAST BLINK – No network contact AND loss of communication with the panel.
ON – Minimum required signal strength is present.
BLINKING – Marginal signal strength is present.
OFF– Installation is not recommended.
FAST BLINK – Hardware Error. Call the AlarmNet Technical Assistance
Center.
– 21 –
DESCRIPTION