Led Operation - Honeywell PRO3200 Installation Manual

Table of Contents

Advertisement

LED Operation

The Two-Reader Module uses two onboard LEDs (D1 and D2) to provide status information during
the power-up sequence as well as during normal operation. The Two-Reader Module also uses two
onboard LEDs (D3 and D4) to indicate reader activity.
Table 3: Onboard LEDs
Mode
Power-up
sequence
Normal
Operation
In addition to the status LEDs, there are six additional relay status LEDs and eight input status LEDs
on board. The input LEDs flash when there is a fault associated with the input. When any relay or input
is energized or ON, its corresponding status LED becomes ON also. The LED remains ON for as long
as the relay is energized.
PRO3200 Two-Reader Module Installation Guide, Document 800-15493
LED D1
LED D2
ON
OFF
OFF
ON
ON
ON
FLASH
ON
FLASH
FLASH
Installing the PRO3200 Two-Reader Module
Description
Start power-up, hardware setup
Testing RAM
Testing ROM and completing
initialization
LED D1 flashes four times after
power-up is completed
This is the processor heartbeat LED. It
flashes once every second. A short ON
time (~20% duty cycle) indicates the
board is offline or has lost serial
communication with the Controller
board. A long ON time (~80% duty
cycle) indicates the board is online and
communicating with the Controller
board.
Flash when there is activity on its Serial
Port.
LED Operation