Honeywell Y8610U Product Data
Honeywell Y8610U Product Data

Honeywell Y8610U Product Data

Intermittent pilot retrofit kit

Advertisement

GENERAL

The Y8610U is a complete kit for converting conventional
standing pilot systems to intermittent pilot systems. It is used
on gas-fired atmospheric furnaces, boilers, and heating
appliances. Not for use on direct vent or power burner
equipment. Meets ANSI Z21.71 standard for automatic
intermittent pilot ignition systems for field installations.

FEATURES

• Y8610U kits can be used with either natural or LP gas.
• Y8610U provides a 90 second maximum ignition trial,
shuts off, waits six minutes nominal, then reinitiates
the pilot ignition sequence. The ignition trial, shutoff,
and wait cycle repeat until the pilot lights or the call
for heat ends.
• Y8610U kits can be used with either natural or LP gas;
it provides timed trial for ignition and 100 percent pilot
shutoff on loss of flame.
Copyright © 1996 Honeywell Inc. • All Rights Reserved
Intermittent Pilot Retrofit Kit
Each kit includes:
- S8610U Intermittent Pilot Module.
- VR8304M Dual Valve Combination Gas Control.
- 392431 Igniter-Sensor.
- 394800-30 Ignition Cable.
- 393691 Natural to LP Gas Conversion Kit.
- Wiring Harness.
- 393690-14 Straight Flange Kit (3/4 in.) .
- Reducer adapters for gas control.
- Adhesive mounting option for S8610.
- Installation hardware.
• Temperature Rating:
- VR8304M: -40°F to 175°F (-40°C to 79°C).
- S8610U: -40°F to 165°F (-40°C to 74°C). (If main
valve current is 1A or less, 175°F (79°C) maximum
ambient applies.)
MODULE
• Uses rectification principle for flame sensing.
• Provides 13 kV peak capacitive discharge spark
output (at 25 pF load).
GAS CONTROL
• Straight through body pattern.
• VR8304M capacity at 1 in. wc pressure drop (0.25 kPa
pressure drop is 270 ft
• Manual ON-OFF valve blocks gas flow into the gas
control when in the OFF position.
• Two main automatic valves-one solenoid-operated,
and one a servo-operated diaphragm system.
IGNITER/SENSOR
• Single electrode made of Kanthal provides both
ignition and flame sensing.
• Rated for 1775°F (968°C) at electrode tip, 1250°F
(677°C) at ceramic insulator.
General ............................................................................... 1
Features .............................................................................. 1
Specifications ...................................................................... 2
Ordering Information ........................................................... 2
Planning the Installation ...................................................... 5
Installation ........................................................................... 5
Checkout ............................................................................. 12
Operation ............................................................................ 13
Troubleshooting .................................................................. 14
ANSI Standards .................................................................. 19
X-XX UL
Y8610U
PRODUCT DATA
3
3
/hr (7.6 m
/hr).
Contents
68-0133-2

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Y8610U

  • Page 1: Table Of Contents

    • Rated for 1775°F (968°C) at electrode tip, 1250°F (677°C) at ceramic insulator. • Y8610U kits can be used with either natural or LP gas. • Y8610U provides a 90 second maximum ignition trial, shuts off, waits six minutes nominal, then reinitiates the pilot ignition sequence.
  • Page 2: Specifications

    If you have additional questions, need further information, or want to comment on our products or services, please write or phone: 1. Your local Honeywell Home and Building Control sales office (check white pages of phone directory). 2. Home and Building Control Customer Logistics Honeywell Inc.,...
  • Page 3 Y8610U INTERMITTENT PILOT RETROFIT KIT VR8304 S8610 INTERMITTENT PILOT MODULE WITH WIRING HARNESS 392431 IGNITER-SENSOR ALSO INCLUDED: ASSEMBLY GROUND • 394800-30 IGNITION CABLE (30 IN. (760 mm)) • 393690-14 STRAIGHT FLANGE KIT • 393691 NATURAL GAS TO LP CONVERSION KIT •...
  • Page 4 Y8610U INTERMITTENT PILOT RETROFIT KIT Pressure Rating: Dual Valve Combination Gas Control Specifications 1/2 psig (3.45 kPa) inlet pressure. Model: VR8304M Dual Valve Combination Gas Control. Terminals: 1/4 in. male quick-connect terminals. Ambient Temperature Rating: -40° to 175°F (-40° to 79°C).
  • Page 5: Planning The Installation

    These be necessary to protect the controls. Proper insulation or applications require Honeywell Home and Building Control shielding should be provided by the appliance manufacturer; Engineering review; contact your Honeywell Sales make sure adequate air circulation is maintained when the Representative for assistance.
  • Page 6 Y8610U INTERMITTENT PILOT RETROFIT KIT Perform the Preinstallation Safety Inspection The preinstallation checks described in ANSI Standard TRANSFORMER THERMOSTAT Z21.71 in the ANSI Standards section must be performed before installing the Y8610. If an unsafe condition is detected, the appliance should be shut off and the owner advised of the COMMON unsafe condition.
  • Page 7 Fig. 7. Mount ground rod on pilot burner. To convert from natural gas to LP, use the 393691 LP Conversion Kit that is included with the Y8610U Intermittent Pilot Retrofit Kit. To convert from LP to natural gas, use the...
  • Page 8 Y8610U INTERMITTENT PILOT RETROFIT KIT Install Adapters to Gas Control (if used) DROP PIPED HORIZONTAL 393690-14 Straight Flange (3/4 in.) CONTROL SUPPLY Remove the seal over the gas control inlet or outlet. Make sure that the O-ring is fitted in the flange groove.
  • Page 9 Y8610U INTERMITTENT PILOT RETROFIT KIT MOUNT IN ONE OF THESE POSITIONS TWO IMPERFECT THREADS GAS CONTROL PIPE THREAD PIPE CORRECT LENGTH APPLY A MODERATE AMOUNT OF PIPE COMPOUND TO PIPE ONLY (LEAVE TWO END THREADS BARE). M3312 Fig. 11. Use moderate amount of pipe compound.
  • Page 10 Y8610U INTERMITTENT PILOT RETROFIT KIT initial power-up. Once this fuse has blown, the module does not Adjust the thermostat heat anticipator to match the work unless the vent damper is connected. system current draw. The current draw equals the total current required for the ignition module (0.2A) plus the...
  • Page 11 Y8610U INTERMITTENT PILOT RETROFIT KIT S8610U VENT DAMPER PLUG GND 24V TH-W MV MV/PV PV (BURNER) SENSE SPARK PV/MV VR8304M COMBINATION WIRING GAS CONTROL HARNESS THERMOSTAT D80D VENT DAMPER LIMIT IGNITER CONTROLLER SENSOR (HOT) PILOT BURNER GROUND POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
  • Page 12: Checkout

    Y8610U INTERMITTENT PILOT RETROFIT KIT CHECKOUT STEP 4: Check Safety Shutoff Operation. • Turn the gas supply off at the manual shutoff valve. • Set the thermostat or controller above the room Check out the gas control system: temperature to call for heat.
  • Page 13: Operation

    Y8610U INTERMITTENT PILOT RETROFIT KIT If the desired outlet gas pressure or gas flow rate • Make sure the main burner lights smoothly without cannot be achieved by adjusting the gas control, check flashback. the gas control inlet pressure using a manometer at the •...
  • Page 14: Troubleshooting

    Y8610U INTERMITTENT PILOT RETROFIT KIT START THERMOSTAT (CONTROLLER) CALLS FOR HEAT STAGE 1 SPARK GENERATOR POWERED TRIAL FOR First valve (pilot) operator opens IGNIITION PILOT BURNER OPERATION Pilot burner lights. After 90 seconds maximum, system shuts off and pilot Module senses valve closes;...
  • Page 15 Y8610U INTERMITTENT PILOT RETROFIT KIT Ensure adequate flame current as follows: STEP 3: Check spark ignition circuit. You need a short jumper wire • Turn off the furnace at the circuit breaker or fuse box. made from ignition cable or other heavily insulated wire.
  • Page 16 Y8610U INTERMITTENT PILOT RETROFIT KIT START NOTE: Before troubleshooting, familiarize yourself with the startup and checkout procedure. TURN OFF GAS SUPPLY. TURN THERMOSTAT (CONTROLLER) TO CALL Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring. Also, FOR HEAT.
  • Page 17 The pilot flame current must measure at least 1uA and steady SMALL BLUE FLAME CHECK FOR LACK OF GAS FROM: or nuisance shutdowns can occur. Use a Honeywell W136 to • CLOGGED ORIFICE FILTER adjust the pilot flame current. • CLOGGED PILOT FILTER Disconnect the furnace power at the service entrance.
  • Page 18 Y8610U INTERMITTENT PILOT RETROFIT KIT ON-OFF (HOT) LIMIT SWITCH CONTROLLER THERMOSTAT TH-W TRANSFORMER (GND) FUSE SPARK DRIVE CIRCUIT FLAME (BUR- SPARK DETECTOR NER) IGNITER CIRCUIT SENSOR HYBRID CIRCUIT BURNER RELAY TIMING GROUND VOLTAGE DRIVERS CIRCUITS POWER SUPPLY MAIN VALVE VENT...
  • Page 19: Ansi Standards

    Y8610U INTERMITTENT PILOT RETROFIT KIT ANSI STANDARDS Exhibit A Recommended Procedure for Safety Inspection of an Existing Appliance Installation as a Preliminary Step to Applying an Automatic Intermittent Pilot System The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in a safe condition for continuing use.
  • Page 20 Y8610U INTERMITTENT PILOT RETROFIT KIT Exhibit B Procedure for Installing Automatic Intermittent Pilot Systems Prior to beginning this procedure, a preliminary examination of the appliance and the automatic intermittent pilot system should be made to determine that the automatic intermittent pilot system can be properly applied to the appliance.