LG - LOAD GATE TIMEOUT

Use the LG command to load the timeout value for the gate relay. This value represents the
number of seconds the Series 1000 energizes the gate relay (time depends on manufacturer
specifications). This usually is not the amount of time the gate remains open. Most systems keep
the gate open until the vehicle has driven through.
1.
At the
prompt, type LG. The system displays: ENTER GATE TIMEOUT:
*
2.
Type the desired number of seconds (1 to 255) for the Series 1000 to energize the gate relay
and press RETURN. Most gate systems use 4 seconds. The
Example:
HCÂ
APVATÂC7VAÂVEIAQWV0Â$
Â
Â
16-2
prompt reappears.
*