Temporary Error Invalid Station Specification Procedure - Mitsubishi FX2N-16CCL-M User Manual

Cc-link master module
Hide thumbs Also See for FX2N-16CCL-M:
Table of Contents

Advertisement

FX2N-16CCL-M CC-Link System Master Block
5.12.3

Temporary error invalid station specification procedure

This section describes the procedure to execute the temporary error invalid station function.
Select whether two or more stations are to be specified as temporary error
invalid stations (SW0003).
(00: Two or more stations, 01 to 15: One station)
Set to ON the request for temporary error invalid station (SB0004).
Turn off the power of temporary error invalid stations, and replace them.
Turn on the power of temporary error invalid stations.
Set to ON the request for cancel of temporary error invalid station (SB0005).
1) Even if the request for temporary error invalid station is executed for a faulty
station, the error information is not cleared.
The temporary error invalid station specification function is effective only to errors
which occur after the specification.
2) The request for temporary error invalid and the request for cancel of temporary
error invalid station are not effective to stations which are specified as error
invalid stations by parameter.
Point
Functions 5
5-24