FX2N-16CCL-M CC-Link System Master Block
5.9

Module Reset Function from Sequence Program

This function resets a module from a sequence program without resetting the PLC or the
master block when the switch settings are changed or an error occurs in the master block.
However, reset is disabled when there is an read module error (when the BFM#A
ON).
Because the PLC is not initialized, operations of other modules are not affected at
all.
The figure below shows a program example for module reset.
M8000
RUN monitor
Reset command
M4 (module reset acceptance completion)
M8000
RUN monitor
Remarks
Change from the mode 0 or the mode 2 to the test mode cannot be executed by the
write request for module reset (BFM#A
For such a change, turn off the power, then turn it on again.
Point
FROM
TO
K0
HA
K4M0
K1
SET
M24
RST
M24
K0
HA
K4M20
K1
b4).
H
Reads from BFM#A
.
H
→ M15 to M0
BFM#A
H
Sets to ON the write request for
module reset.
Sets to OFF the write request for
module reset.
Writes to BFM#A
.
H
M35 to M20 → BFM#A
H
5-18
Functions 5
b0 is
H