Emerson Unidrive M400 User Manual page 54

Variable speed ac drive for induction motors
Hide thumbs Also See for Unidrive M400:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
5
Analog input 2
Default function
Type of input
Mode controlled by....
Operating in voltage mode (default)
Full scale voltage range
Maximum offset
Absolute maximum voltage range
Input resistance
Resolution
Sample / update period
Operating in current mode
Current ranges
Maximum offset
Absolute maximum applied voltage (reverse bias)
Resolution
Sample / update period
Operating in digital mode
Logic mode controlled by...
Absolute maximum applied voltage range
Impedance
Input threshold
Sample / update period
6
0V common
Function
7
Analog output 1
8
Analog output 2
Terminal 7 default function
Terminal 8 default function
Type of output
Mode controlled by...
Operating in voltage mode (default)
Voltage range
Maximum offset
Minimum load resistance
Protection
Operating in current mode
Current ranges
Maximum load resistance
Operating in digital output mode
Nominal maximum output current
Voltage range
Common to all modes
Resolution
Sample / update period
54
Electrical
Getting
Basic
Running
installation
started
parameters
the motor
Frequency reference
Unipolar single-ended analog voltage, unipolar single-ended current or digital input
(positive or negative logic).
Pr 07.011
0 V to +10 V ±3 %
±30 mV
-18 V to +30 V relative to 0 V
100 k Ω
11 bits
5 ms
0 to 20 mA ±4 %, 20 to 0 mA ±4 %,
4 to 20 mA ±4 %, 20 to 4 mA ±4 %
250 µA
-18 V to +30 V relative to 0 V
11 bits
5 ms
Pr 08.010
-18 V to +30 V relative to 0 V
6.8 kΩ
10 V ±0.8 V from IEC 61131-2
2 ms when routed to destinations Pr 06.035 or Pr 06.036, otherwise 6 ms.
Common connection for all external devices
Frequency output
Motor active current
Unipolar single-ended analog voltage, unipolar single-ended current or digital output.
Pr 07.021, Pr 07.024
0 to +10 V ±5 %
15 mV
500 Ω
Short circuit relative to 0 V
0 to 20 mA ±4 %,
4 to 20 mA ±4 %
500 Ω
50 mA
0 V to +24 V
0.1 %
5 ms
NV Media Card
Onboard
Optimization
Operation
PLC
Advanced
Technical data Diagnostics