This trip indicates that a power stage over-temperature has been detected. From the sub-trip 'xxyzz', the Thermistor
location is identified by 'zz'.
Power system
Recommended actions:
Check enclosure / drive fans are still functioning correctly
Force the heatsink fans to run at maximum speed
22
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Reduce the drive switching frequency
Reduce duty cycle
Increase acceleration / deceleration rates
Reduce motor load
Check the derating tables and confirm the drive is correctly sized for the application.
Use a drive with larger current / power rating
Rectifier over temperature
OHt Rectifier
The Oht Rectifier trip indicates that a rectifier over-temperature has been detected. The thermistor location can be identified
from the sub-trip number.
Source
Power
system
Recommend actions:
102
Check the motor and motor cable insulation with an insulation tester
Fit an output line reactor or sinusoidal filter
Force the heatsink fans to run at maximum speed by setting Pr 06.045 = 1
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Increase acceleration / deceleration rates
Reduce duty cycle
Reduce motor load
OI ac
Instantaneous output over current detected
The instantaneous drive output current has exceeded VM_DRIVE_CURRENT_MAX.
Source
Control
system
3
Recommended actions/checks:
Increase acceleration/deceleration rate
If seen during auto-tune reduce the voltage boost
Check for short circuit on the output cabling
Check integrity of the motor insulation using an insulation tester
Is the motor cable length within limits for the frame size?
Reduce the values in the frequency loop gain parameters - (Pr 03.010, 03.011, 03.012) or (Pr 03.013, 03.014, 03.015)
Reduce the values in the current loop gain parameters
182
Electrical
Getting
Basic
Running
installation
started
parameters
the motor
Source
xx
01
xx
y
Power module
Rectifier
number
number
xx
y
00
0
NV Media Card
Onboard
Optimization
Operation
y
zz
0
zz
Thermistor location in the drive defined by zz
zz
zz
Thermistor location defined by zz
zz
Instantaneous over-current trip when the measured a.c. current
00
exceeds VM_DRIVE_CURRENT[MAX].
Advanced
Technical data
Diagnostics
PLC
parameters
Description
Description
Description
Unidrive M400 User Guide
UL listing
information
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents