Safety
Product
Mechanical
information
information
installation
OHt Power
Power stage over temperature
This trip indicates that a power stage over-temperature has been detected. From the sub-trip 'xxyzz', the Thermistor
location is identified by 'zz'.
Power system
Recommended actions:
•
Check enclosure / drive fans are still functioning correctly
•
Force the heatsink fans to run at maximum speed
22
•
Check enclosure ventilation paths
•
Check enclosure door filters
•
Increase ventilation
•
Reduce the drive switching frequency
•
Reduce duty cycle
•
Increase acceleration / deceleration rates
•
Reduce motor load
•
Check the derating tables and confirm the drive is correctly sized for the application.
•
Use a drive with larger current / power rating
Rectifier over temperature
OHt Rectifier
The Oht Rectifier trip indicates that a rectifier over-temperature has been detected. The thermistor location can be identified
from the sub-trip number.
Source
Power
system
Recommend actions:
102
•
Check the motor and motor cable insulation with an insulation tester
•
Fit an output line reactor or sinusoidal filter
•
Force the heatsink fans to run at maximum speed by setting Pr 06.045 = 1
•
Check enclosure / drive fans are still functioning correctly
•
Check enclosure ventilation paths
•
Check enclosure door filters
•
Increase ventilation
•
Increase acceleration / deceleration rates
•
Reduce duty cycle
•
Reduce motor load
OI ac
Instantaneous output over current detected
The instantaneous drive output current has exceeded VM_DRIVE_CURRENT_MAX.
Source
Control
system
3
Recommended actions/checks:
•
Increase acceleration/deceleration rate
•
If seen during auto-tune reduce the voltage boost
•
Check for short circuit on the output cabling
•
Check integrity of the motor insulation using an insulation tester
•
Is the motor cable length within limits for the frame size?
•
Reduce the values in the frequency loop gain parameters - (Pr 03.010, 03.011, 03.012) or (Pr 03.013, 03.014, 03.015)
•
Reduce the values in the current loop gain parameters
182
Electrical
Getting
Basic
Running
installation
started
parameters
the motor
Source
xx
01
xx
y
Power module
Rectifier
number
number
xx
y
00
0
NV Media Card
Onboard
Optimization
Operation
y
zz
0
zz
Thermistor location in the drive defined by zz
zz
zz
Thermistor location defined by zz
zz
Instantaneous over-current trip when the measured a.c. current
00
exceeds VM_DRIVE_CURRENT[MAX].
Advanced
Technical data
Diagnostics
PLC
parameters
Description
Description
Description
Unidrive M400 User Guide
UL listing
information
Issue Number: 2