5.5. Online configuration
Input Calibration (DE Transmitters) - Correct Input (Zero), LRV, URV; Reset Corrects
Set-Up On Bench
A typical bench set-up is shown at right.
Connect the MC Toolkit as indicated, and
establish communication with the
transmitter.
For these procedures, components in the
current loop are not critical, provided that
they support reliable communication
between the transmitter and the MC Toolkit.
If a Honeywell Pressure Transmitter is being
calibrated, positioning (leveling) is important,
because the meter body contains fluids that
can affect zero sensing.
Enter
From the DE MAIN MENU, select Configure to call up the DE
(configure)
CONFIGURE display.
values for
a. Use the PV Units to select the appropriate Engineering
LRV and
Units.
URV
b. Using the keyboard, enter the desired LRV and URV
values.
c. Select the Send button to copy all newly entered values to
the transmitter. When the copy operation is complete,
Send will be displayed in half intensity.
84
MC Toolkit (MCT404) User Manual
Revision 3