4. Managing HART Devices using FDC Application Software
4.6. Online configuration

Executing methods on a device

To execute methods on devices, perform the following steps.
Note: For example, consider the following scenario to execute Loop test.
1.
On the Device Home page, tap Functions tab.
2.
Tap Online > Select.
3.
The Device Configuration page appears which displays the top and bottom panes.
4.
Navigate to the desired menu. The bottom pane will display items under that menu.
5.
Select a method from the list. For example, Loop Test.
6.
Tap Execute.
A warning message appears displaying a message that loop must be removed from the automatic
control.
7.
Tap OK.
8.
The Loop Test dialog box appears displaying the information to choose analog output level.
9.
Choose the analog output level and tap OK.
Note: To cancel the method execution, tap Abort.
10. A message appears displaying the information that the output value of the device is fixed.
11. Tap OK.
12. The Loop Test dialog box appears displaying information to choose analog output level.
13. In the Choose analog output level combo box, tap to select End.
14. Tap OK.
The method is executed successfully.