Table 1-1: Maximum cable lengths between sensor and transmitter
Cable type
Micro Motion 4-wire
Micro Motion 9-wire
User-supplied 4-wire
1.4
Install the Model 3300 or Model 3500 in the
panel
Refer to
1. Insert the Model 3300 or Model 3500 through the cutout.
2. Slide the frame over the housing.
3. Insert the posts on the brackets into the rails on the housing.
4. Tighten the screws evenly to 10 to 14 inch-pounds (1,13 to 1,38 Nm) to ensure a
watertight seal between the gasket and the panel.
Figure 1-6: Panel installation steps
Installation Manual
Figure 1-6
and follow these steps:
Step 2
Step 3
Wire gauge
Not applicable
Not applicable
VDC 22 AWG (0.35 mm
2
)
VDC 20 AWG (0.5 mm
2
)
2
VDC 18 AWG (0.8 mm
)
RS-485 22 AWG (0.35 mm
2
larger
Step 1
Step 4
Maximum length
•
1000 ft (300 m) without
Ex-approval
•
500 ft (150 m) with
IIC-rated sensors
•
1000 ft (300 m) with
IIB-rated sensors
60 ft (20 m)
300 ft (90 m)
500 ft (150 m)
1000 ft (300 m)
) or
1000 ft (300 m)
Planning
9