6

Related Parameters

The following parameters are used to set up the drive for operation with the option.
Confirm proper setting of all parameters in
No.
(Addr. Hex)
b1-01
Frequency Reference
(180)
Selection 1
<1>
b1-02
(181)
Run Command Selection 1
<1>
F6-01
Communications Error
(3A2)
Operation Selection
F6-02
External Fault from Comm.
(3A3)
Option Detection Selection
F6-03
External Fault from Comm.
(3A4)
Option Operation Selection
F6-06
Torque Reference/Torque
(3A7)
Limit Selection from Comm.
Option
<5>
Multi-Step Speed Enable/
F6-07
Disable Selection when
(3A8)
NefRef/ComRef is Selected
YASKAWA ELECTRIC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual
Table 8 Related Parameters
Name
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option
4: Pulse Input (Terminal RP)
Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option
Determines drive response when a bUS error is
detected during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Alarm and Run at d1-04
5: Alarm and Ramp to stop
Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation
Determines drive response for external fault input
(EF0) detection during PROFIBUS communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Torque reference/torque limit via network
communications are disabled.
1: Torque reference/torque limit via network
communications are enabled.
0: Multi-step speed reference disabled (F7
functionality)
1: Multi-step speed reference allowed (V7
functionality)
Table 8
before starting network communications.
Description
<2>
<2> <3> <4>
<3> <4>
<2>
<6>
6 Related Parameters
Default: 1
Range: 0 to 4
(Set to 3 for
SI-P3)
Default: 1
Range: 0 to 3
(Set to 3 for
SI-P3)
Default: 1
Range: 0 to 5
Default: 0
Range: 0, 1
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Values
25

Hide quick links:

Advertisement