YASKAWA 1000 Series Installation Manual page 28

Profibus-dp
Hide thumbs Also See for 1000 Series:
Table of Contents

Advertisement

6 Related Parameters
No.
(Addr. Hex)
F7-78
(792)
PZD9 Read
<3> <7>
F7-79
(793)
PZD10 Read
<3> <7>
<1> Set b1-02 to 3 to start and stop the drive through the PROFIBUS-DP network. Set b1-01 to 3 to control the
frequency reference of the drive via the PROFIBUS-DP network.
<2> Take proper safety measures, such as installing an emergency stop switch, when setting F6-03 to 3 or 4, as the
drive will continue operation when detecting a fault.
<3> Available in the A1000 software versions PRG: 1021 and later.
<4> Refer to the instruction manual of a specific drive to determine if settings 4 and 5 are available in the drive.
<5> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines
whether the value is read as the torque limit value (d5-01 = 0) or as the torque reference value (d5-01 = 1). In
CLV/PM, this value is read as the torque limit.
<6> Default setting specifies that the torque reference or torque limit is to be provided via network communications
(F6-06 = 1). The motor may not rotate if no torque reference or torque limit is supplied from the PLC.
<7> Available in the option software versions PRG: 2103 and later.
<8> All node addresses must be unique. Node addresses 0, 1, and 2 are typically reserved for control, maintenance,
and diagnostic equipment. The "Err" LED will illuminate when a value of 0 or a value greater than 125 is entered.
<9> Cycle power for setting changes to take effect.
<10> Requires also setting bit 0 to 1 to issue Run command. Refer to the option Technical Manual for more
information.
<11> When writing this parameter to the drive through the PROFIBUS-DP network, the parameter is validated by
automatically executing the Enter command.
28
Name
Sets MEMOBUS/Modbus address for PZD9 Read
(PPO Read).
The value of 0 to 2 disables the PZD9 Read.
Sets MEMOBUS/Modbus address for PZD10 Read
(PPO Read).
The value of 0 to 2 disables the PZD10 Read.
YASKAWA ELECTRIC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual
Description
Values
Default: 0H
Min: 0H
Max: FFFFH
Default: 0H
Min: 0H
Max: FFFFH