YASKAWA 1000 Series Installation Manual page 26

Profibus-dp
Hide thumbs Also See for 1000 Series:
Table of Contents

Advertisement

6 Related Parameters
No.
(Addr. Hex)
F6-08
Reset Communication
(36A)
Parameters
F6-14
(3BB)
bUS Error Auto Reset
<3> <7>
F6-30
PROFIBUS-DP Node
(3CB)
Address
<8> <9>
F6-31
PROFIBUS-DP Clear Mode
(3CC)
Selection
F6-32
PROFIBUS-DP Data Format
(3CD)
Selection
<7> <9>
F7-16
Communication Loss
(3F4)
Time-out
<3> <7>
F7-60
(780)
PZD1 Write
<3> <7>
F7-61
(781)
PZD2 Write
<3> <7>
F7-62
(780)
PZD3 Write
<3> <7>
F7-63
(783)
PZD4 Write
<3> <7>
26
Name
Determines which F6- and F7- parameters
are reset to default values when initializing the drive
using A1-03.
0: Do not reset parameters
1: Reset parameters
Note: Setting this parameter does not affect
communication-related parameters. Setting this
parameter only determines if communication-related
parameters
(F6- and F7-) are also reset when initializing
with A1-03.
Enables or disables the bUS Error Auto Reset.
0: Disabled
1: Enabled
Sets the node address.
Selects the action to take when a "Clear Mode"
command is received.
0: Resets to 0
1: Maintains the previous value
0: PPO Type
1: Conventional
2: PPO (w/bit 0)
3: PPO Type (Auto Enter)
4: Conventional (Auto Enter)
5: PPO (w/bit0, Auto Enter)
Sets the time-out value for communication loss
detection in tenths of a second. A value of 0 disables
the connection time-out.
Example: An entered value of 100 represents 10.0
seconds.
Sets MEMOBUS/Modbus address for PZD1 Write
(PPO Write).
The value of 0 to 2 enables the PZD1 Write as STW.
Sets MEMOBUS/Modbus address for PZD2 Write
(PPO Write).
The value of 0 to 2 enables the PZD2 Write as HSW.
Sets MEMOBUS/Modbus address for PZD3 Write
(PPO Write).
The value of 0 to 2 disables the PZD3 Write.
Sets MEMOBUS/Modbus address for PZD4 Write
(PPO Write).
The value of 0 to 2 disables the PZD4 Write.
YASKAWA ELECTRIC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual
Description
<3> <10>
<3> <11>
<3> <11>
<3> <10> <11>
Values
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Min: 0
Max: 125
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 5
Default: 0.0
Min: 0.0
Max: 30.0
Default: 0H
Min: 0H
Max: FFFFH
Default: 0H
Min: 0H
Max: FFFFH
Default: 0H
Min: 0H
Max: FFFFH
Default: 0H
Min: 0H
Max: FFFFH

Hide quick links: