Programming
2.
Scroll to parameter group 5-1* Digital Inputs and
press [OK].
Illustration 6.10 Parameter Group Display Example
3.
Scroll to 5-10 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
6
6
Start is shown.
Illustration 6.11 Function Choice Display Example
6.4 International/North American Default
Parameter Settings
Setting 0-03 Regional Settings to [0] International or [1]
North America changes the default settings for some
parameters. Table 6.1 lists those parameters that are
effected.
Parameter
0-03 Regional
Settings
0-71 Date Format
0-72 Time Format
1-20 Motor Power
[kW]
1-21 Motor Power
[HP]
1-22 Motor Voltage 230 V/400 V/575 V
1-23 Motor
Frequency
3-03 Maximum
Reference
3-04 Reference
Function
70
Operating Instructions
14.7%
0.00A
Digital In/Out
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
14.7%
0.00A
Digital Inputs
5-10 Terminal 18 Digital
Input
[8]] Start
International default
North American
parameter value
default parameter
value
International
North America
DD-MM-YYYY
MM/DD/YYYY
24 h
12 h
See Note 1
See Note 1
See Note 2
See Note 2
208 V/460 V/575 V
50 Hz
60 Hz
50 Hz
60 Hz
Sum
External/Preset
Danfoss A/S © Rev. 05/2014 All rights reserved.
Parameter
1(1)
4-13 Motor Speed
5-**
High Limit [RPM]
See Note 3
4-14 Motor Speed
High Limit [Hz]
See Note 4
4-19 Max Output
Frequency
4-53 Warning Speed
High
5-12 Terminal 27
Digital Input
5-40 Function Relay [2] Drive ready
6-15 Terminal 53
1(1)
High Ref./Feedb.
5-1*
Value
6-50 Terminal 42
Output
14-20 Reset Mode
22-85 Speed at
Design Point [RPM]
See Note 3
22-86 Speed at
Design Point [Hz]
Table 6.1 International/North American Default Parameter
Settings
Note 1: 1-20 Motor Power [kW] is only visible when 0-03 Regional
Settings is set to [0] International.
Note 2: 1-21 Motor Power [HP], is only visible when 0-03 Regional
Settings is set to [1] North America.
Note 3: This parameter is only visible when 0-02 Motor Speed Unit is
set to [0] RPM.
Note 4: This parameter is only visible when 0-02 Motor Speed Unit is
set to [1] Hz.
Note 5: The default value depends on the number of motor poles. For
a 4 poled motor, the international default value is 1500 RPM and for
a 2 poled motor, 3000 RPM. The corresponding values for North
America is 1800 and 3600 RPM.
Changes made to default settings are stored and available
for viewing in the Quick Menu along with any
programming entered into parameters.
1.
Press [Quick Menu].
2.
Scroll to Q5 Changes Made and press [OK].
3.
Select Q5-2 Since Factory Setting to view all
programming changes or Q5-1 Last 10 Changes
for the most recent.
International default
North American
parameter value
default parameter
value
1500 RPM
1800 RPM
50 Hz
60 Hz
100 Hz
120 Hz
1500 RPM
1800 RPM
Coast inverse
External interlock
No alarm
50
60
Output frequency
Speed 4-20 mA
Manual reset
Infinite auto reset
1500 RPM
1800 RPM
50 Hz
60 Hz
MG16J202