4.3.2 Required Initial Frequency Converter
Programming
NOTICE
If the wizard is run, ignore the following.
Frequency converters require basic operational
programming before running for best performance. This
4
4
requires entering motor-nameplate data for the motor
being operated and the minimum and maximum motor
speeds. Enter data in accordance with the following
procedure. Parameter settings recommended are intended
for start-up and checkout purposes. Application settings
may vary. See chapter 5 User Interface for detailed
instructions on entering data via the LCP.
Enter data with power ON, but before operating the
frequency converter.
1.
Press [Main Menu] twice on the LCP.
2.
Press the navigation keys to scroll to parameter
group 0-** Operation/Display and press [OK].
Illustration 4.26 Main Menu
3.
Press the navigation keys to scroll to parameter
group 0-0* Basic Settings and press [OK].
Illustration 4.27 Operation/Display
4.
Press the navigation keys to scroll to
0-03 Regional Settings and press [OK].
60
Operating Instructions
1107 RPM
3.84 A
Main menu
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
0.0%
0.00A
Operation / Display
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
LCP Display
*
0-3
*
LCP Custom Readout
Danfoss A/S © Rev. 05/2014 All rights reserved.
Illustration 4.28 Basic Settings
5.
Press the navigation keys to select [0] Interna-
tional or [1] North America as appropriate and
press [OK]. (This changes the default settings for
a number of basic parameters. See
chapter 6.4 International/North American Default
Parameter Settings for a complete list.)
6.
Press [Quick Menu] on the LCP.
7.
Press the navigation keys to scroll to parameter
group Q2 Quick Setup and press [OK].
1 (1)
Illustration 4.29 Quick Menus
8.
Select the language and press [OK].
9.
A jumper wire should be in place between
control terminals 12 and 27. If this is the case,
leave 5-12 Terminal 27 Digital Input at factory
default. Otherwise select No Operation. For
1(1)
frequency converters with an optional Danfoss
0-
**
bypass, no jumper wire is required.
10.
Set 3-02 Minimum Reference
11.
Set 3-03 Maximum Reference
12.
Set 3-41 Ramp 1 Ramp Up Time
13.
Set 3-42 Ramp 1 Ramp Down Time
14.
Set 3-13 Reference Site. Linked to Hand/Auto*
Local Remote.
0.0%
0.00A
Basic Settings
0-03 Regional Settings
[0] International
13.7%
13.0A
Quick Menus
Q1 My Personal Menu
Q2 Quick Setup
Q5 Changes Made
Q6 Loggings
1(1)
0-0
*
1(1)
MG16J202

Advertisement

Table of Contents
loading

Table of Contents